The PRG-6004 series analog signal transmitter is an isolator with two signal inputs and one signal output. It automatically compares the magnitudes of the two input signals to select one for output (with user-selectable high- or low-output mode), or it allows the user to manually select one input signal via a digital/on-off signal or level signal, before isolating and outputting the selected signal.

img
产品详情 技术参数 下载

Close
  • 产品对比
Total X Clear all

去对比

Basic Parameters
Number of channels Two in, one out
Output accuracy (20°C) 0.2% F.S.
Control Method Automatic high/low level output; digital signal control output
Hysteresis ≤0.5%
Temperature drift 50ppm/K
Response time ≤0.05s (0~90%) (TYP)
Dielectric strength 1500V AC/1min, 2mA
Insulation resistance 500V DC Greater than 100 MΩ
Electromagnetic Compatibility Complies with GB/T 18268 (IEC 61326-1)
Weight About 200 grams
Driving capability 250 VAC/2 A or 30 VDC/2 A
Connected field devices Current source
Input data
Input signal 0 mA to 20 mA, 0 to 10 V
Input impedance Voltage type ≤100 Ω, current type ≥100 kΩ
Output data
Output signal 0~10V, 0mA~20mA,
Output impedance Voltage type ≤ 500 Ω, current type ≥ 10 kΩ
Power supply
Supply voltage (Ue) 24 Vdc ±10%
Power Protection Reverse Power Protection
Power consumption <2W
Power Supply Method Independent power supply
Power Connection Method Terminal power supply, base power supply
Size
Depth 110mm
Height 108mm
Width 18.3mm
Housing
Materials PC+ABS flame retardant
Protection Level IP20
Flame-retardant rating UL94/V0
Color black
EMC data
Electrical Fast Transient/Burst Immunity Standards: IEC 61326-1; Class A
Surge (Impulse) Immunity Standards: IEC 61326-1; Class B
Radio-frequency electromagnetic field radiation immunity Standards: IEC 61326-1; Compliance with Essential Requirements
Electrostatic Discharge Immunity Standards: IEC 61326-1; Class A
Immunity to Conducted Disturbances Induced by Radio-Frequency Fields Standards: IEC 61326-1; Compliance with Essential Requirements
Low-Frequency Common-Mode Conduction Standards: IEC 61326-1; Compliance with Essential Requirements
Operating Environment
Continuous operating temperature ‘-20℃~+60℃
Storage temperature -40℃ to +80℃
Relative humidity <90% RH (no condensation)
Environmental Requirements The surrounding environment shall be free from severe vibration, impact, and electromagnetic interference such as high currents and sparks. The air shall not contain any corrosive media that can attack chromium, nickel, or silver platings, nor shall it contain flammable or explosive substances.
Connection Parameters
Wire cross-sectional area range 0.5~2.5 mm²
   
Minimum Wire Cross-Sectional Area AWG 12
Maximum Conductor Cross-Sectional Area AWG 24
Wire stripping length 8mm
Thread M3
Connection method Screw connection
Minimum Tightening Torque 0.5 Nm
Maximum Tightening Torque 0.6 Nm
Install
Installation Method DIN 35 mm rail mounting