The PRG-6004 series analog signal transmitter is an isolator with two signal inputs and one signal output. It automatically compares the magnitudes of the two input signals to select one for output (with user-selectable high- or low-output mode), or it allows the user to manually select one input signal via a digital/on-off signal or level signal, before isolating and outputting the selected signal.
产品详情
技术参数
下载

Close
- 产品对比
去对比
| Basic Parameters | |
| Number of channels | Two in, one out |
| Output accuracy (20°C) | 0.2% F.S. |
| Control Method | Automatic high/low level output; digital signal control output |
| Hysteresis | ≤0.5% |
| Temperature drift | 50ppm/K |
| Response time | ≤0.05s (0~90%) (TYP) |
| Dielectric strength | 1500V AC/1min, 2mA |
| Insulation resistance | 500V DC Greater than 100 MΩ |
| Electromagnetic Compatibility | Complies with GB/T 18268 (IEC 61326-1) |
| Weight | About 200 grams |
| Driving capability | 250 VAC/2 A or 30 VDC/2 A |
| Connected field devices | Current source |
| Input data | |
| Input signal | 0 mA to 20 mA, 0 to 10 V |
| Input impedance | Voltage type ≤100 Ω, current type ≥100 kΩ |
| Output data | |
| Output signal | 0~10V, 0mA~20mA, |
| Output impedance | Voltage type ≤ 500 Ω, current type ≥ 10 kΩ |
| Power supply | |
| Supply voltage (Ue) | 24 Vdc ±10% |
| Power Protection | Reverse Power Protection |
| Power consumption | <2W |
| Power Supply Method | Independent power supply |
| Power Connection Method | Terminal power supply, base power supply |
| Size | |
| Depth | 110mm |
| Height | 108mm |
| Width | 18.3mm |
| Housing | |
| Materials | PC+ABS flame retardant |
| Protection Level | IP20 |
| Flame-retardant rating | UL94/V0 |
| Color | black |
| EMC data | |
| Electrical Fast Transient/Burst Immunity | Standards: IEC 61326-1; Class A |
| Surge (Impulse) Immunity | Standards: IEC 61326-1; Class B |
| Radio-frequency electromagnetic field radiation immunity | Standards: IEC 61326-1; Compliance with Essential Requirements |
| Electrostatic Discharge Immunity | Standards: IEC 61326-1; Class A |
| Immunity to Conducted Disturbances Induced by Radio-Frequency Fields | Standards: IEC 61326-1; Compliance with Essential Requirements |
| Low-Frequency Common-Mode Conduction | Standards: IEC 61326-1; Compliance with Essential Requirements |
| Operating Environment | |
| Continuous operating temperature | ‘-20℃~+60℃ |
| Storage temperature | -40℃ to +80℃ |
| Relative humidity | <90% RH (no condensation) |
| Environmental Requirements | The surrounding environment shall be free from severe vibration, impact, and electromagnetic interference such as high currents and sparks. The air shall not contain any corrosive media that can attack chromium, nickel, or silver platings, nor shall it contain flammable or explosive substances. |
| Connection Parameters | |
| Wire cross-sectional area range | 0.5~2.5 mm² |
| Minimum Wire Cross-Sectional Area AWG | 12 |
| Maximum Conductor Cross-Sectional Area AWG | 24 |
| Wire stripping length | 8mm |
| Thread | M3 |
| Connection method | Screw connection |
| Minimum Tightening Torque | 0.5 Nm |
| Maximum Tightening Torque | 0.6 Nm |
| Install | |
| Installation Method | DIN 35 mm rail mounting |