产品中心

+
  • 9.png
  • e6090690-6231-4301-9ee3-5c08d173e55c_366xaf(8).jpg
  • 39571b05-d476-412b-859c-d1f0be15a8f5_366xaf(8).jpg

PB-12-(S3) Industrial Data Transmission System Signal Surge Protector

img

所属分类:

PB Series

● Ultra-thin 12.5 mm width design for space-saving installation, with low contact resistance and low impedance ● Surge withstand capability up to 10 kA (8/20 µs) ● Terminal grounding; mounting via DIN 35 mm rail

线制:

2

标称放电电流In:

10 kA

适用电压:

连接方式:

Plug-in

防爆:

遥信功能 :

None

适用配电系统 :

img
产品详情 技术参数 下载

Close
  • 产品对比
Total X Clear all

去对比

Basic Parameters
Number of protective lines 3 lines
Rated operating voltage Un (DC) 12V
Maximum Operating Voltage Uc (DC) 18V
Rated Operating Current IL (DC) 500mA
Nominal discharge current IN (8/20 µs) 5KA
Maximum discharge current Imax (8/20 µs) 10KA
Impulse current Iinp (10/350 µs) 2.5KA
Total surge current Iinp (10/350 µs) 5KA
Voltage protection level UP (8/20 µs), line-to-line, line-to-ground 40V/600V
Voltage protection level UP (8/20 µs), line-to-line, line-to-ground 20V/600V
Bandwidth (-0.5 dB) 10MHz
Response time tA 1ns
Channel Resistance (per line) 1 ohm
Leakage current <10 µA
Applicable Compatible with signal inputs such as RS485 and RS232.
Size
Depth 78.2mm
Height 90mm
Width 12.7mm
Housing
Materials Flame-retardant ABS
Protection Level IP20
Flame-retardant rating PA66/V0
Color blue
Standards/Procedures
Test standards are met. GB/T 18802.21-2016/IEC 61643-21:2012
Lightning Protection Performance Testing Beijing Lightning Protection Facility Inspection Service Center
Operating Environment
Continuous operating temperature -20℃~+60℃
Storage temperature -40℃~+80℃
Relative humidity 10%~90%
Environmental Requirements The surrounding environment shall be free from severe vibration, impact, and electromagnetic interference such as high currents and sparks. The air shall not contain any corrosive media that can attack chromium, nickel, or silver platings, nor shall it contain flammable or explosive substances.
Connection Parameters
Wire cross-sectional area range 0.5~2.5 mm²
Minimum Wire Cross-Sectional Area AWG 12
Maximum Conductor Cross-Sectional Area AWG 24
Wire stripping length 8mm
Thread M3
Connection method Screw connection
Minimum Tightening Torque 0.5 Nm
Maximum Tightening Torque 0.6 Nm
Install
Installation Method DIN 35 mm rail mounting

文件名称

文件大小

所属分类

上传时间

预览下载