  • 2ac6e4ce-8810-4586-b6ee-d7efd9d1c4c7_640xaf(4).jpg

PB-D220-P 220V DC power surge protector

Picture Name

Classification:

PB series

Suitable for DC power supply, suitable for installation in lightning protection zones LPZ2 and LPZ3.

Wire system:

Nominal discharge current In:

10kA,20kA

Applicable voltage:

Connection mode:

Push-in connection

Explosion proof:

Remote signaling function:

have

Applicable distribution system:

Product Details Technical parameters Download

Close
  • 产品对比
Total X Clear all

Contrast

Basic parameters

Lightning protection category

T2/T3

Nominal voltageDC)

220V

Maximum Continuous Operating Voltage Uc(DC)

320V

Nominal discharge current IN(8/20us)

10KA/20KA

Maximum discharge currentImax(8/20us)

20KA/40KA

Voltage protection level UP(8/20us)

≤1000V

Front fuse or air switch

16A

Response timetA

≤25ns

Suit

Suitable for various DC power systems, DC distribution panels, DC power supply equipment, DC distribution boxes, electronic information system cabinets, and output terminals of secondary power equipment

Size

Depth

90mm

Height

58mm

Width

18mm

Housing

Material

PBT flame retardant

Protection grade

IP20

Flame retardant grade

PA66/V0

Colour

Red

Standards/Procedures

Testing standards meet

GB/T 18802.21-2016/IEC 61643-21-2012

Lightning protection performance test

Beijing Lightning Protection Facilities Testing Service Center

Usage environment

Continuous operating temperature

-20℃~+60℃

Storage temperature

-40℃~+80℃

Relative humidity

10%~90%

Environmental requirements

There should be no strong vibrations, impacts, high currents, sparks or other electromagnetic induction effects in the surrounding environment. The air should not contain media that corrode chromium, nickel, and silver coatings, and should not contain flammable or explosive substances

Connection parameters

Available cross-sectional range of wires

1.5~6mm²

Minimum conductor cross-section AWG

12

Maximum conductor cross-section AWG

24

Strip length

8mm

Thread

M3

Connection method

Screw connection

Minimum tightening torque

0.5 Nm

Maximum tightening torque

0.6 Nm

Install

Installation method

DIN35mm guide rail installation