Basic Parameters |
|
| Number of channels | 3 in, 3 out |
| Output accuracy (20°C) | Accuracy: ±0.2%, ±0.5% |
| Response time | <400ms |
| Dielectric strength | 1500V AC/1min, 2mA |
| Insulation resistance | Greater than 100 MΩ at 500 VDC |
| Electromagnetic Compatibility | Complies with GB/T 18268 (IEC 61326-1) |
| Weight | About 100 grams |
| Connected field devices | Current source |
| Overload capacity | Can withstand 2 times the rated value (continuous), 10 times the rated value (10 s) |
| Power consumption | Approximately 2 VA |
Input data |
|
| Input signal | 0~10A |
| Input Load | Current transformer PT: ≤0.2 VA |
Output data |
|
| Output signal | Output current: 0 to 20 mA DC, 4 to 20 mA DC (Load resistance = 10 Vdc / output current); Output voltage: 0 to 10 Vdc (Load resistance = Input voltage / 10 mA DC) |
| Output ripple | ≤0.5% RO |
Size |
|
| Length | 109mm |
| Height | 119mm |
| Width | 75mm |
Housing |
|
| Materials | Flame-retardant ABS |
| Protection Level | IP20 |
| Flame-retardant rating | UL94/V0 |
| Color | black |
EMC data |
|
| Electrical Fast Transient/Burst Immunity | Standards: IEC 61326-1; Class A |
| Surge (Impulse) Immunity | Standards: IEC 61326-1; Class B |
| Radio-frequency electromagnetic field radiation immunity | Standards: IEC 61326-1; Compliance with Essential Requirements |
| Electrostatic Discharge Immunity | Standards: IEC 61326-1; Class A |
| Immunity to Conducted Disturbances Induced by Radio-Frequency Fields | Standards: IEC 61326-1; Compliance with Essential Requirements |
| Low-Frequency Common-Mode Conduction | Standards: IEC 61326-1; Compliance with Essential Requirements |
Operating Environment |
|
| Operating temperature | 0–50°C / Less than 80% relative humidity (non-condensing) |
| Storage temperature | ‘-20°C to +70°C / Less than 70% relative humidity (non-condensing) |
| Relative humidity | <90% RH (no condensation) |
| Environmental Requirements | The surrounding environment shall be free from severe vibration, impact, and electromagnetic interference such as high currents and sparks. The air shall not contain any corrosive media that can attack chromium, nickel, or silver plating, nor shall it contain flammable or explosive substances. |
Connection Parameters |
|
| Wire cross-sectional area range | 0.5~2.5 mm² |
| Minimum Wire Cross-Sectional Area AWG | 12 |
| Maximum Conductor Cross-Sectional Area AWG | 24 |
| Wire stripping length | 8mm |
| Thread | M3 |
| Connection method | Screw connection |
| Minimum Tightening Torque | 0.5 Nm |
| Maximum Tightening Torque | 0.6 Nm |
Install |
|
| Installation Method | DIN 35 mm rail mounting |