An active power transmitter is a device that isolates and converts the active power parameter in the power grid into a linear DC analog signal.

Single-phase two-wire,Three-phase three-wire,Three-phase four-wire

0-1Aac,0-5Aac,User-defined

0~5V,0~10V,0~20mA,4~20mA,User-defined

24 Vdc,48 Vdc,220Vac,User-defined

img
产品详情 技术参数 下载

Close
  • 产品对比
Total X Clear all

去对比

Basic Parameters
Output accuracy (20°C) ±0.5%
Response time <400ms
Dielectric strength 1500V AC/1min, 2mA
Insulation resistance Greater than 100 MΩ at 500 VDC
Electromagnetic Compatibility Complies with GB/T 18268 (IEC 61326-1)
Weight About 100 grams
Connected field devices Current source
Overload capacity Voltage: Withstand 2 times the rated value (continuous) Current: 10 times the rated value (10 s)
Power consumption Approximately 4 VA
Input data
Input signal 1A; 5A; 100V, 220V, 380V
Input Load Voltage transformer PT: ≤ 0.1 VA
Current transformer CT: ≤ 0.2 VA
Output data
Output signal Output current: 0 to 20 mA DC, 4 to 20 mA DC
(Load resistance = 10 Vdc / output current); Output voltage: 0 to 10 Vdc, 0 to 5 Vdc
(Load resistance = Input voltage / 10 mA DC)
Output ripple ≤0.5% RO
Size
Length 109mm
Height 119mm
Width 75mm
Housing
Materials Flame-retardant ABS
Protection Level IP20
Flame-retardant rating UL94/V0
Color black
EMC data
Electrical Fast Transient/Burst Immunity Standards: IEC 61326-1; Class A
Surge (Impulse) Immunity Standards: IEC 61326-1; Class B
Radio-frequency electromagnetic field radiation immunity Standards: IEC 61326-1; Compliance with Essential Requirements
Electrostatic Discharge Immunity Standards: IEC 61326-1; Class A
Immunity to Conducted Disturbances Induced by Radio-Frequency Fields Standards: IEC 61326-1; Compliance with Essential Requirements
Low-Frequency Common-Mode Conduction Standards: IEC 61326-1; Compliance with Essential Requirements
Operating Environment
Operating temperature 0–50°C / Less than 80% relative humidity (non-condensing)
Storage temperature ‘-20°C to +70°C / Less than 70% relative humidity (non-condensing)
Relative humidity <90% RH (no condensation)
Environmental Requirements The surrounding environment shall be free from severe vibration, impact, and electromagnetic interference such as high currents and sparks. The air shall not contain any corrosive media that can attack chromium, nickel, or silver platings, nor shall it contain flammable or explosive substances.
Connection Parameters
Wire cross-sectional area range 0.5~2.5 mm²
Minimum Wire Cross-Sectional Area AWG 12
Maximum Conductor Cross-Sectional Area AWG 24
Wire stripping length 8mm
Thread M3
Connection method Screw connection
Minimum Tightening Torque 0.5 Nm
Maximum Tightening Torque 0.6 Nm
Install
Installation Method DIN 35 mm rail mounting