The PASR-8000-3A1B is a safety relay designed for emergency stop buttons, safety door interlock switches, and DIO signal inputs in SIS systems, featuring three NC (normally closed) auxiliary output contacts. It supports single- or dual-channel operation, with manual or automatic reset, and includes inter-channel short-circuit monitoring.

输入设备:

Emergency Stop Button/Safety Door

供电电压:

24V DC

输出触点数:

3NO+1NC

复位方式:

Automatic / Manual Reset

触点切换容量:

5A

img
产品详情 技术参数 下载

Close
  • 产品对比
Total X Clear all

去对比

Basic Parameters
Number of channels 1
Electromagnetic Compatibility EN 60947, EN 61000-6-2, EN 61000-6-4
Status Display 1 green LED
Start Button Monitoring Manual Start/Automatic Start
Rated Insulation Voltage 250 V (Pollution Degree 2 in accordance with IEC 60947-5-1)
Rated impulse withstand voltage 6000 V (Category 2 overvoltage as defined in IEC 60947-5-1)
Dielectric strength 1500V AC, 1 min
Time
Absorption buffer time ≤300ms
Release buffer time ≤30ms
Recovery time ≤100ms
Short-term power interruption 20ms
Contact resistance ≤100 mΩ
Applicable DO signal (SIS system)
Input parameters
Number of channels 1
Input signal DO signal
Input current ≤50mA (24VDC)
Wire resistance ≤15Ω
Input device SIS system DO signal matching
Output data
Number of contacts 3NO+1NC
Output signal Relay output
Contact material AgSnO + 0.2 µm Au
Contact Fuse Protection 10A (Internal Fuse Blow Protection)
Contact capacity AC-15, 5A/230V; AC-13, 5A/24V
Power supply
Power supply voltage 24VDC
Current loss ≤90mA (24VDC)
Voltage tolerance 0.85~1.1
Power Protection Reverse Power Protection
Power Supply Method Independent power supply
Power Connection Method Terminal power supply
Size
Height 114.5mm
Width 99mm
Thickness 22.5mm
Housing
Materials Flame-retardant ABS
Protection Level IP20
Flame-retardant rating UL94/V0
Color Gray + Yellow
EMC data
Electrical Fast Transient/Burst Immunity Standards: IEC 61326-1; Class A
Surge (Impulse) Immunity Standards: IEC 61326-1; Class B
Radio-frequency electromagnetic field radiation immunity Standards: IEC 61326-1; Compliance with Essential Requirements
Electrostatic Discharge Immunity Standards: IEC 61326-1; Class A
Immunity to Conducted Disturbances Induced by Radio-Frequency Fields Standards: IEC 61326-1; Compliance with Essential Requirements
Low-Frequency Common-Mode Conduction Standards: IEC 61326-1; Compliance with Essential Requirements
Meets the standard BS EN 62061:2015, ISO 13849-1:2015, ISO 13849-2:2012, IEC EN 60204-1, ISO 13849-1
Safety Integrity Level (SIL) EN 954-1, Maximum Safety Integrity Level 4
Performance Level (PL) ISO 13849-1:2015, PL e
Operating Environment
Continuous operating temperature -20℃~+60℃
Storage temperature '-40℃ to +85℃
Relative humidity <90% RH (no condensation)
Environmental Requirements The surrounding environment shall be free from severe vibration, impact, and electromagnetic interference such as high currents and sparks. The air shall not contain any corrosive media that can attack chromium, nickel, or silver platings, nor shall it contain flammable or explosive substances.
Connection Parameters
Wire cross-sectional area range 0.5~2.5 mm²
Minimum Wire Cross-Sectional Area AWG 12
Maximum Conductor Cross-Sectional Area AWG 24
Wire stripping length 8mm
Thread M3
Connection method Screw connection
Minimum Tightening Torque 0.5 Nm
Maximum Tightening Torque 0.6 Nm
Install
Installation Method DIN 35 mm rail mounting

文件名称