Products
DRG-6003 Current/voltage signal alarm setter
Classification:
DRG-6000 series
The current input alarm setter provides isolation power to the on-site transmitter and receives a 4mA~20mADC (or 4mA~20mA current source signal) generated by the transmitter, which is sampled by AD and sent to the MCU The MCU controls two relay alarm outputs and one 4mA~20mA current signal output based on user set range, alarm point, alarm mode and other parameters.
Product Details
Technical parameters
Download

Close
- 产品对比
Contrast
| General | |
| Output accuracy (20 ° C) | 0.2%F.S. |
| Temperature drift | 50ppm/K |
| Response time | ≤20ms |
| Insulation strength | 1500V AC/1min,2mA |
| Insulation resistance | Above 100M Ω at 500VDC |
| Electromagnetic compatibility | Compliant with GB/T18268 (IEC61326-1) |
| Weight | About 150g |
| Drive capacity | 250VAC/2A or 30VDC/2A |
| Load capacity | Resistive load |
| Connected on-site equipment | Current source, two or three wire transmitter |
| Input data | |
| Input signal | 4mA~20mA, voltage signal |
| Output data | |
| Output signal | 4mA~20mA |
| Output load | 0~500Ω |
| Power supply | |
| Supply voltage(Ue) | 20V~35VDC |
| Power protection | Reverse protection of power supply |
| Power consumption | About 2W |
| Power supply mode | Independent power supply |
| Power connecting mode | Terminal power supply;Base power supply |
| Overall dimension | |
| Depth | 110mm |
| Height | 108mm |
| Width | 18.3mm |
| Housing | |
| Material | PC+ABSflame retardant |
| Degree of protection | IP20 |
| Flammability rating | UL94/V0 |
| Colour | Black |
| EMC data | |
| Electrical fast transient/burst immunity | Compliant with:IEC 61326-1;A-leve |
| Surge immunity | Compliant with:IEC 61326-1;B-leve |
| Radiated,radio-frequency,electromagnetic field immunity | Compliant with:IEC 61326-1;conform to basic requirements |
| Electrostatic discharge immunity | Compliant with:IEC 61326-1;A-leve |
| Immunity to conducted disturbances, induced by radio-frequency fields | Compliant with:IEC 61326-1;conform to basic requirements |
| Low frequency common mode conduction | Compliant with:IEC 61326-1;conform to basic requirements |
| Operating conditions | |
| Continuous operating temperature | ﹣20℃~﹢60℃ |
| Storage temperature | ﹣40℃~+80℃ |
| Relative humidity | <90% RH (no condensate) |
| Environmental requirements | There should be no strong vibrations, impacts, high currents, sparks or other electromagnetic induction effects in the surrounding environment. The air should not contain media that corrode chromium, nickel, and silver coatings, and should not contain flammable or explosive substances |
| Connection data | |
| Conductor cross section solid range | 0.5~2.5mm² |
| Conductor cross section AWG min. | 12 |
| Conductor cross section AWG max. | 24 |
| Stripping length | 8mm |
| Screw thread | M3 |
| Connection method | Screw connection |
| Tightening torque min. | 0.5 Nm |
| Tightening torque max. | 0.6 Nm |
| Installation | |
| Installation method | DIN35mm |
File Name
File Size
Classification
Upload time
Download
207.1KB
Signal isolator
2023-09-19
File Name
Classification
Download