PASR-9000-AB Suitable for monitoring emergency stop switch and safety door
Classification:
PASR-9000 series
PASR-9000-AB is suitable for emergency stop buttons, safety door control switches, and safety relays with 2 NO (normally open) safety output contacts and 2 NC (normally closed) auxiliary output contacts. It supports single and dual channel operation, manual or automatic reset, and has channel to channel short circuit monitoring function.
Input device:
Emergency stop button/safety door
Supply voltage:
24V DC
Number of output contacts:
2NO+2NC
Reset mode:
Auto/manual reset
Contact switching capacity:
5A

- 产品对比
Contrast
| General | |
| Number of channels | Dual channel input |
| Switch capacity | |
| Rated heating current Ith | 5A |
| Insurance level | 6A fast or 4A slow |
| Usage category | AC-15,DC-13 |
| Time | |
| Dual channel input time | Unlimited |
| Safe output time under rated voltage | Manual start 35ms |
| Safe disconnection time under rated voltage | 10ms |
| Contact material and structure | AgSnO+0.2um Au, forced open contact |
| Contact resistance | ≤100mΩ |
| Mechanical life | 10 million times |
| Operation frequency | 6 times/minute |
| Status display | Three green LEDs |
| Start button monitoring | Manual start/automatic start |
| Rated insulation voltage | 300V (pollution level 2 according to IEC60947-5-1) |
| Rated impulse withstand voltage | 2500V (Class 2 overvoltage according to IEC60947-5-1) |
| Applicable | Emergency stop switch, safety door |
| Input data | |
| Input channel | Dual channel input |
| Input current | ≤50mA |
| Wire resistance | ≤15Ω |
| Output data | |
| Output capacity | 2NO+2NC |
| Output channel | 2-channel normally open output (13-14, 23-24) |
| 2-channel normally closed output (31-32, 41-42) | |
| Power supply | |
| Supply voltage | 24VDC |
| Voltage range | 85%~110% |
| Module power consumption | ≤ 90mA (24V DC) |
| Overall dimension | |
| Height | 114.5mm |
| Width | 99mm |
| Thickness | 22.5mm |
| Housing | |
| Material | ABSflame retardant |
| Degree of protection | IP20 |
| Flammability rating | UL94/V0 |
| Colour | Grey+Yellow |
| EMC data | |
| Electrical fast transient/burst immunity | Compliant with:IEC 61326-1;A-leve |
| Surge immunity | Compliant with:IEC 61326-1;B-leve |
| Radiated,radio-frequency,electromagnetic field immunity | Compliant with:IEC 61326-1;conform to basic requirements |
| Electrostatic discharge immunity | Compliant with:IEC 61326-1;A-leve |
| Immunity to conducted disturbances, induced by radio-frequency fields | Compliant with:IEC 61326-1;conform to basic requirements |
| Low frequency common mode conduction | Compliant with:IEC 61326-1;conform to basic requirements |
| Compliant with standards | BS EN 62061:2015,ISO 13849-1:2015,ISO 13849-2:2012, IEC EN 60204-1, ISO 13849-1 |
| Safety Integrity Level (SIL) | EN954-1, maximum safety control level 4 |
| Performance level (PL) | ISO 13849-1:2015,PLe |
| Operating conditions | |
| Continuous operating temperature | ﹣20℃~﹢60℃ |
| Storage temperature | ﹣40℃~+85℃ |
| Relative humidity | <90% RH (no condensate) |
| Environmental requirements | There should be no strong vibrations, impacts, high currents, sparks or other electromagnetic induction effects in the surrounding environment. The air should not contain media that corrode chromium, nickel, and silver coatings, and should not contain flammable or explosive substances |
| Connection data | |
| Conductor cross section solid range | 0.5~2.5mm² |
| Conductor cross section AWG min. | 12 |
| Conductor cross section AWG max. | 24 |
| Stripping length | 8mm |
| Screw thread | M3 |
| Connection method | Screw connection |
| Tightening torque min. | 0.5 Nm |
| Tightening torque max. | 0.6 Nm |
| Installation | |
| Installation method | DIN35mm |