Installation of Surge Protective Devices
Principles for the Installation of Surge Protective Devices
1. Application Protection Distance
Surge protector The application protection distance refers to the straight-line distance between any two instruments or devices outdoors.
When the horizontal straight-line distance of a signal cable above ground exceeds 100 m or the vertical distance exceeds 10 m, surge protective devices should be installed at both ends of the field instruments and the control room instruments.
2. Instruments equipped with surge protectors
1) Surge protectors shall be installed at the field instrument terminals of the safety instrumented system.
2) Surge protectors shall be installed at the field end of the transmitter;
3) Surge protectors shall be installed at the instrument terminals of field electrical signal actuators, such as electric transducers, electric valve positioners, and solenoid valves.
4) Surge protectors shall be installed at the field terminals of resistance temperature detectors.
5) Surge protective devices shall be installed at the field end of electronic switches;
Surge protective devices shall be installed at the control room end of all the above-mentioned systems.
3. Instruments without surge protectors
1) Surge protectors are not required at the field end of thermocouples;
2) Surge protective devices shall not be installed at the field end of contact switches;
3) Surge protective devices are not required for pump and motor signals originating from the switchgear room and the electrical control room.
Types of Surge Protectors
The selection of a surge protective device shall be determined based on the protection objective, signal type, installation location, and installation method.
For two-wire, three-wire, and four-wire 4–20 mA signal instruments with a nominal supply voltage of 24 VDC, the loop DC power supply lines are considered signal power supplies and shall be classified as signal instrument equipment, not as DC power supply equipment; accordingly, they shall be equipped in accordance with the requirements for signal instruments. Surge protector (Selection between two-wire and three-wire systems PB—24-T2 , select when using the four-wire system PB—5—T2 )。
DC power supply units fall under the category of DC power supplies and shall be equipped with surge protective devices in accordance with DC power supply requirements.
The AC power supply for four-wire AC-powered instruments shall be of the AC power supply type and shall be provided in accordance with the requirements for AC power supplies. Nanjing Paroken Technology Co., Ltd. Surge protector (For example, PB-40/320-2P ).
Multi-signal-channel surge protectors should not be used.
A properly selected surge protective device, whether used to protect AC power systems or signal and data systems—such as fieldbus, 4–20 mA signaling, telecommunications, and network communications—shall not compromise or alter the characteristics and reliability of the application system.
Parameters of Signal Line Surge Protective Devices
1. Maximum Continuous Operating Voltage Uc
The maximum continuous operating voltage, Uc—also referred to as the maximum working signal voltage—is the maximum RMS or DC signal voltage that a surge protective device can withstand during long-term operation. It is also the maximum voltage between lines or between a line and ground, under rated leakage current conditions, that will not impair the normal operation of the circuit in which the device is installed.
For 24 V DC-powered instruments, due to factors such as DC power supply voltage fluctuations and load variations, the maximum signal voltage ranges from 30 to 36 V DC; therefore, the maximum continuous operating voltage shall be Uc ≥ 36 V.
2. Maximum signal current Ic
The maximum signal current (working current) is the maximum operating signal current of the circuit in which the surge protective device is installed.
For 4–20 mA field instruments with two-wire, three-wire, or four-wire configurations (including HART communication signals), the maximum signal current shall be: Ic ≥ 150 mA.
For 24 V DC power supply lines, such as those powering solenoid valves, ultrasonic instruments, and combustible gas detectors, the maximum signal current shall be: Ic ≥ 600 mA.
3. Rated discharge current In
The nominal discharge current In is the maximum surge current (Max. Anti-surge Current Capacity) in kA (8/20 μs) that a surge protective device can normally withstand. It refers to the maximum discharge current that the surge protective device can handle without sustaining damage when subjected to the specified number of test cycles using the standard 8/20 μs impulse waveform. For signal instruments, a nominal discharge current In greater than 1 kA is sufficient to meet typical protection requirements; specifications such as 5 kA or 10 kA may be selected.
Parameters of Signal Line Surge Protective Devices
4. Voltage Protection Level Up
The voltage protection level is the clamping voltage of a surge protective device when it diverts surge current; it is also referred to as the pass-through voltage or limiting voltage. It represents the peak voltage at the output of the surge protective device when subjected to a 6 kV/3 kA, 8/20 μs surge waveform generator or other specified test voltage and current conditions.
For instruments operating at 24 VDC, the surge protective device’s voltage protection level shall be 60 V. The clamping voltage of the selected surge protective device should not be excessively high; it is generally recommended to be about 2 to 2.5 times the operating or signal voltage of the equipment being protected. Moreover, the voltage protection level must be lower than the withstand voltage of the protected instrument.
5. Response Time
Response time is the delay between the moment the standard test waveform voltage is applied to the surge protective device and the moment the device actually conducts and discharges. For signal-type surge protective devices, the response time shall be ≤5 ns.
6. Operating Frequency
The operating frequency is the highest signal frequency that can pass through the circuit connected to the surge protective device during normal operation. For instrument signals, including “smart” instruments, an operating frequency of 20 kHz or less is generally negligible.