Principle of the Resistance Temperature Detector


A resistance thermometer is a temperature-sensing device whose operating principle is based on the temperature-dependent variation of electrical resistance in metallic materials. This variation may be linear or nonlinear, depending on the material used.

Metal resistors generally exhibit a positive temperature coefficient; in this case, the variation of resistance with temperature can be expressed by the following equation: RT = R0(1 + aT + bT² + ...), where RT is the resistance at temperature T, R0 is the resistance at 0°C, T is the measured temperature, and a and b are constants that depend on the specific metal.

A resistance temperature detector (RTD) is a sensor that measures temperature by detecting the change in electrical resistance of a metal as a function of temperature. When the purity of the metal remains constant, the resistance–temperature relationship exhibits excellent reproducibility. Common RTD materials include platinum (Pt), copper (Cu), nickel (Ni), and tungsten (W). These metallic wires are typically wound around heat-resistant, electrically insulating glass to form wire-wound temperature sensors; the figure shows the resistance–temperature characteristic curve for such sensors.

Metals used as resistance-temperature detector (RTD) materials are required to have stable resistance values and good linearity of resistance with temperature; platinum is the most commonly used material. RTDs are typically specified with nominal resistance values of 50 Ω and 100 Ω at 0°C; however, 50-Ω RTDs are seldom used and are being phased out, with 100-Ω RTDs now being the predominant choice.

The operating temperature range for resistance thermometers is as follows: low temperatures, −200 to +100°C; medium temperatures, 0 to 350°C; and high temperatures, 0 to 500°C. When measuring temperature with a resistance thermometer, an external power supply must be applied to maintain a specified current through the resistor; the voltage drop across the resistor due to this current is then measured, thereby determining the temperature. Consequently, resistance thermometers offer high measurement accuracy, particularly for ambient-temperature measurements, making them more suitable than thermocouple thermometers in such applications.

To provide mechanical and chemical protection for resistance thermometers, they are typically housed within a protective sheath during operation. Particularly in industrial applications, where the thermometer is exposed to corrosive gases, careful selection of the sheath material is essential to ensure effective protection. The chosen sheath must meet the following requirements: it must exhibit sufficient thermal and pressure resistance; it must be highly resistant to corrosion by the process medium and must not chemically react with the medium; it must remain intact under rapid temperature fluctuations during sealing; it must demonstrate strong vibration and shock resistance; and it must facilitate rapid heat transfer from the external environment to the resistance element.

Temperature-measuring instruments based on resistance thermometers include bridge circuits, DC potentiometers, electronic automatic-balancing measuring instruments, moving-coil ratio-type measuring instruments, moving-coil type measuring instruments, and digital thermometers. In the measurement circuits of these instruments, to ensure varying levels of measurement accuracy, resistance thermometers may be connected using two-wire, three-wire, or four-wire configurations.

The Parokeng resistance temperature detector signal isolator enables isolation and conversion of field RTD signals into either a 1:1 RTD signal or an analog signal.

Product features of the Parokon temperature isolation transmitter:

》Power and alarm status indicator

》Input and output signals are configurable.

》Optional surge protection and RS485 interface

Isolation between input/output/power channels

》Centralized power supply for the base, with hot-swappable support

》Two-wire and three-wire input compatible