产品中心

+
  • 2ac6e4ce-8810-4586-b6ee-d7efd9d1c4c7._640xaf.jpg

PB-D24-P 24V DC Power Surge Protector

img

所属分类:

PB Series

● DC power surge protectors are designed to safeguard secondary and tertiary DC power systems and connected electrical equipment from damage caused by lightning-induced overvoltages and transient overvoltages. Thanks to the incorporation of temperature-controlled circuit-breaking technology and a built-in overcurrent protection circuit, the risk of fire is completely eliminated. ● These devices are suitable for use at the output terminals of various DC power systems, DC distribution panels, DC power supply equipment, DC distribution boxes, electronic information system cabinets, and secondary power supply equipment (including DC circuits in fire control rooms).

线制:

标称放电电流In:

10 kA

适用电压:

24V

连接方式:

Screw-type

防爆:

遥信功能 :

None

适用配电系统 :

img
产品详情 技术参数 下载

Close
  • 产品对比
Total X Clear all

去对比

Basic Parameters
Lightning Protection Category T2/T3
Nominal Voltage (DC) 5V
Maximum Continuous Operating Voltage Uc (DC) 6V
Nominal discharge current IN (8/20 µs) 5KA
Maximum discharge current Imax (8/20 µs) 10KA
Voltage Protection Level UP (8/20 µs) 40V/600V
Front-mounted fuse or circuit breaker  
Response time tA 1ns
Applicable Suitable for the output terminals of various DC power systems, DC distribution panels, DC power supply equipment, DC distribution boxes, electronic information system cabinets, and secondary power supply equipment.
Size
Depth 90mm
Height 58mm
Width 18mm
Housing
Materials Flame-retardant PBT
Protection Level IP20
Flame-retardant rating PA66/V0
Color Red
Standards/Procedures
Test standards are met. GB/T 18802.21-2016/IEC 61643-21:2012
Lightning Protection Performance Testing Beijing Lightning Protection Facility Inspection Service Center
Operating Environment
Continuous operating temperature -20℃~+60℃
Storage temperature -40℃~+80℃
Relative humidity 10%~90%
Environmental Requirements The surrounding environment shall be free from severe vibration, impact, and electromagnetic interference such as high currents and sparks. The air shall not contain any corrosive media that can attack chromium, nickel, or silver plating, nor shall it contain flammable or explosive substances.
Connection Parameters
Wire cross-sectional area range 1.5~6 mm²
Minimum Wire Cross-Sectional Area AWG 12
Maximum Conductor Cross-Sectional Area AWG 24
Wire stripping length 8mm
Thread M3
Connection method Screw connection
Minimum Tightening Torque 0.5 Nm
Maximum Tightening Torque 0.6 Nm
Install
Installation Method DIN 35 mm rail mounting

文件名称

文件大小

所属分类

上传时间

预览下载