PB-D24-P 24V DC Power Surge Protector
所属分类:
PB Series
● DC power surge protectors are designed to safeguard secondary and tertiary DC power systems and connected electrical equipment from damage caused by lightning-induced overvoltages and transient overvoltages. Thanks to the incorporation of temperature-controlled circuit-breaking technology and a built-in overcurrent protection circuit, the risk of fire is completely eliminated. ● These devices are suitable for use at the output terminals of various DC power systems, DC distribution panels, DC power supply equipment, DC distribution boxes, electronic information system cabinets, and secondary power supply equipment (including DC circuits in fire control rooms).
线制:
标称放电电流In:
10 kA
适用电压:
24V
连接方式:
Screw-type
防爆:
遥信功能 :
None
适用配电系统 :

- 产品对比
去对比
Basic Parameters |
|
| Lightning Protection Category | T2/T3 |
| Nominal Voltage (DC) | 5V |
| Maximum Continuous Operating Voltage Uc (DC) | 6V |
| Nominal discharge current IN (8/20 µs) | 5KA |
| Maximum discharge current Imax (8/20 µs) | 10KA |
| Voltage Protection Level UP (8/20 µs) | 40V/600V |
| Front-mounted fuse or circuit breaker | |
| Response time tA | 1ns |
| Applicable | Suitable for the output terminals of various DC power systems, DC distribution panels, DC power supply equipment, DC distribution boxes, electronic information system cabinets, and secondary power supply equipment. |
Size |
|
| Depth | 90mm |
| Height | 58mm |
| Width | 18mm |
Housing |
|
| Materials | Flame-retardant PBT |
| Protection Level | IP20 |
| Flame-retardant rating | PA66/V0 |
| Color | Red |
Standards/Procedures |
|
| Test standards are met. | GB/T 18802.21-2016/IEC 61643-21:2012 |
| Lightning Protection Performance Testing | Beijing Lightning Protection Facility Inspection Service Center |
Operating Environment |
|
| Continuous operating temperature | -20℃~+60℃ |
| Storage temperature | -40℃~+80℃ |
| Relative humidity | 10%~90% |
| Environmental Requirements | The surrounding environment shall be free from severe vibration, impact, and electromagnetic interference such as high currents and sparks. The air shall not contain any corrosive media that can attack chromium, nickel, or silver plating, nor shall it contain flammable or explosive substances. |
Connection Parameters |
|
| Wire cross-sectional area range | 1.5~6 mm² |
| Minimum Wire Cross-Sectional Area AWG | 12 |
| Maximum Conductor Cross-Sectional Area AWG | 24 |
| Wire stripping length | 8mm |
| Thread | M3 |
| Connection method | Screw connection |
| Minimum Tightening Torque | 0.5 Nm |
| Maximum Tightening Torque | 0.6 Nm |
Install |
|
| Installation Method | DIN 35 mm rail mounting |