Products
PB-D24-P 24V DC power surge protector
Classification:
PB series
DC power surge protector is used to prevent damage to secondary and tertiary DC power systems and electrical equipment caused by lightning overvoltage and transient overvoltage. Due to the use of temperature controlled circuit breaker technology and built-in overcurrent protection circuit, the occurrence of a fire is completely avoided. Applicable to various DC power supply systems, DC distribution panels, DC power supply equipment, DC distribution boxes, electronic information system cabinets, and output terminals of secondary power supply equipment (DC lines in the fire control room).
Wire system:
Nominal discharge current In:
10kA
Applicable voltage:
24V
Connection mode:
Screw connection
Explosion proof:
Remote signaling function:
not have
Applicable distribution system:

- 产品对比
Contrast
|
Basic parameters |
|
|
Lightning protection category |
T2/T3 |
|
Nominal voltage(DC) |
5V |
|
Maximum Continuous Operating Voltage Uc(DC) |
6V |
|
Nominal discharge current IN(8/20us) |
5KA |
|
Maximum discharge currentImax(8/20us) |
10KA |
|
Voltage protection level UP(8/20us) |
40V/600V |
|
Front fuse or air switch |
|
|
Response timetA |
1ns |
|
Suit |
Suitable for various DC power systems, DC distribution panels, DC power supply equipment, DC distribution boxes, electronic information system cabinets, and output terminals of secondary power equipment |
|
Size |
|
|
Depth |
90mm |
|
Height |
58mm |
|
Width |
18mm |
|
Housing |
|
|
Material |
Flame retardant PBT |
|
Protection grade |
IP20 |
|
Flame retardant grade |
PA66/V0 |
|
Colour |
Red |
|
Standards/Procedures |
|
|
Testing standards meet |
GB/T 18802.21-2016/IEC 61643-21-2012 |
|
Lightning protection performance test |
Beijing Lightning Protection Facilities Testing Service Center |
|
Usage environment |
|
|
Continuous operating temperature |
-20℃~+60℃ |
|
Storage temperature |
-40℃~+80℃ |
|
Relative humidity |
10%~90% |
|
Environmental requirements |
There should be no strong vibrations, impacts, high currents, sparks or other electromagnetic induction effects in the surrounding environment. The air should not contain media that corrode chromium, nickel, and silver coatings, and should not contain flammable or explosive substances |
|
Connection parameters |
|
|
Available cross-sectional range of wires |
1.5~6mm² |
|
Minimum conductor cross-section AWG |
12 |
|
Maximum conductor cross-section AWG |
24 |
|
Strip length |
8mm |
|
Thread |
M3 |
|
Connection method |
Screw connection |
|
Minimum tightening torque |
0.5 Nm |
|
Maximum tightening torque |
0.6 Nm |
|
Install |
|
|
Installation method |
DIN35mm guide rail installation |
File Name
File Size
Classification
Upload time
Download