PD-20 Single-Phase DC Current Transmitter
所属分类:
PD Series
The single-phase AC current isolation transmitter primarily employs isolation components to electrically isolate the input AC current signal, while providing a linear output in standard industrial formats such as 0–5 V, 0–10 V, 0–20 mA, and 4–20 mA. It delivers safer, more reliable, and highly accurate monitoring signals for automated monitoring systems. This product is widely used in applications such as power grid monitoring, motor signal monitoring, and railway system signal monitoring.
Single-phase
0-30 Vdc,0-500 Vdc,0-100 Vdc,0–400 Vdc,User-defined
0~5V,0~10V,1~5V,0~20mA,4~20mA,0~10mA,User-defined
12Vdc,24 Vdc,220 Vdc,User-defined,220Vac,110 Vdc

- 产品对比
去对比
Basic Parameters |
||
| Output accuracy (20°C) | Class 0.5 | |
| Response time | ≤100ms | |
| Dielectric strength | 1500V AC/1min, 2mA | |
| Insulation resistance | Greater than 100 MΩ at 500 VDC | |
| Electromagnetic Compatibility | Complies with GB/T 18268 (IEC 61326-1) | |
| Weight | About 150 grams | |
| Auxiliary power supply | +12 Vdc, +15 Vdc, +24 Vdc, 220 Vac/dc, etc. | |
| Load capacity | Voltage output ≥ 2 kΩ, current output ≤ 250 Ω | |
| Static Power Consumption | ≤0.3W | |
| Rated Power Consumption | ≤0.7W | |
| Withstand Voltage Isolation | DC2500V | |
| Temperature coefficient | ≤500 ppm/°C | |
| Lightning Surge | 2000V at the power input, 500V at the output | |
Input data |
||
| Input signal | DC 5A~600A | |
Output data |
||
| Output signal | 0–5 V, 0–10 V, 0–20 mA, 4–20 mA (optional) | |
Size |
||
| Depth | 110mm 110mm 100mm | |
| Height | 82mm 85mm 89mm | |
| Width | 28mm 28mm 28mm | |
| Product aperture | ∅6mm ∅22mm ∅35mm | |
Housing |
||
| Materials | Flame-retardant ABS | |
| Protection Level | IP20 | |
| Flame-retardant rating | UL94/V0 | |
| Color | Gray | |
EMC data |
||
| Electrical Fast Transient/Burst Immunity | Standards: IEC 61326-1; Class A | |
| Surge (Impulse) Immunity | Standards: IEC 61326-1; Class B | |
| Radio-frequency electromagnetic field radiation immunity | Standards: IEC 61326-1; Compliance with Essential Requirements | |
| Electrostatic Discharge Immunity | Standards: IEC 61326-1; Class A | |
| Immunity to Conducted Disturbances Induced by Radio-Frequency Fields | Standards: IEC 61326-1; Compliance with Essential Requirements | |
| Low-Frequency Common-Mode Conduction | Standards: IEC 61326-1; Compliance with Essential Requirements | |
Operating Environment |
||
| Operating temperature | -10~60℃ | |
| Storage temperature | -20°C to +70°C / Less than 70% relative humidity (non-condensing) | |
| Relative humidity | <90% RH (no condensation) | |
| Environmental Requirements | The surrounding environment shall be free from severe vibration, impact, and electromagnetic interference such as high currents and sparks. The air shall not contain any corrosive media that can attack chromium, nickel, or silver plating, nor shall it contain flammable or explosive substances. | |
Connection Parameters |
||
| Wire cross-sectional area range | 0.5~2.5 mm² | |
| Minimum Wire Cross-Sectional Area AWG | 12 | |
| Maximum Conductor Cross-Sectional Area AWG | 24 | |
| Wire stripping length | 8mm | |
| Thread | M3 | |
| Connection method | Screw connection | |
| Minimum Tightening Torque | 0.5 Nm | |
| Maximum Tightening Torque | 0.6 Nm | |
Install |
||
| Installation Method | DIN 35 mm rail mounting | |