PD-20 Single-Phase DC Current Transmitter

img

所属分类:

PD Series

The single-phase AC current isolation transmitter primarily employs isolation components to electrically isolate the input AC current signal, while providing a linear output in standard industrial formats such as 0–5 V, 0–10 V, 0–20 mA, and 4–20 mA. It delivers safer, more reliable, and highly accurate monitoring signals for automated monitoring systems. This product is widely used in applications such as power grid monitoring, motor signal monitoring, and railway system signal monitoring.

Single-phase

0-30 Vdc,0-500 Vdc,0-100 Vdc,0–400 Vdc,User-defined

0~5V,0~10V,1~5V,0~20mA,4~20mA,0~10mA,User-defined

12Vdc,24 Vdc,220 Vdc,User-defined,220Vac,110 Vdc

img
产品详情 技术参数 下载

Close
  • 产品对比
Total X Clear all

去对比

Basic Parameters
 
Output accuracy (20°C) Class 0.5  
Response time ≤100ms  
Dielectric strength 1500V AC/1min, 2mA  
Insulation resistance Greater than 100 MΩ at 500 VDC  
Electromagnetic Compatibility Complies with GB/T 18268 (IEC 61326-1)  
Weight About 150 grams  
Auxiliary power supply +12 Vdc, +15 Vdc, +24 Vdc, 220 Vac/dc, etc.  
Load capacity Voltage output ≥ 2 kΩ, current output ≤ 250 Ω  
Static Power Consumption ≤0.3W  
Rated Power Consumption ≤0.7W  
Withstand Voltage Isolation DC2500V  
Temperature coefficient ≤500 ppm/°C  
Lightning Surge 2000V at the power input, 500V at the output  
Input data
 
Input signal DC 5A~600A  
Output data
 
Output signal 0–5 V, 0–10 V, 0–20 mA, 4–20 mA (optional)  
Size
 
Depth 110mm 110mm 100mm  
Height 82mm 85mm 89mm  
Width 28mm 28mm 28mm  
Product aperture ∅6mm ∅22mm ∅35mm  
Housing
 
Materials Flame-retardant ABS  
Protection Level IP20  
Flame-retardant rating UL94/V0  
Color Gray  
EMC data
 
Electrical Fast Transient/Burst Immunity Standards: IEC 61326-1; Class A  
Surge (Impulse) Immunity Standards: IEC 61326-1; Class B  
Radio-frequency electromagnetic field radiation immunity Standards: IEC 61326-1; Compliance with Essential Requirements  
Electrostatic Discharge Immunity Standards: IEC 61326-1; Class A  
Immunity to Conducted Disturbances Induced by Radio-Frequency Fields Standards: IEC 61326-1; Compliance with Essential Requirements  
Low-Frequency Common-Mode Conduction Standards: IEC 61326-1; Compliance with Essential Requirements  
Operating Environment
 
Operating temperature -10~60℃  
Storage temperature -20°C to +70°C / Less than 70% relative humidity (non-condensing)  
Relative humidity <90% RH (no condensation)  
Environmental Requirements The surrounding environment shall be free from severe vibration, impact, and electromagnetic interference such as high currents and sparks. The air shall not contain any corrosive media that can attack chromium, nickel, or silver plating, nor shall it contain flammable or explosive substances.  
Connection Parameters
 
Wire cross-sectional area range 0.5~2.5 mm²  
Minimum Wire Cross-Sectional Area AWG 12  
Maximum Conductor Cross-Sectional Area AWG 24  
Wire stripping length 8mm  
Thread M3  
Connection method Screw connection  
Minimum Tightening Torque 0.5 Nm  
Maximum Tightening Torque 0.6 Nm  
Install
 
Installation Method DIN 35 mm rail mounting  

文件名称

文件大小

所属分类

上传时间

预览下载

1.4MB

Electricity transducer

2023-09-27

< 1 >

文件名称

所属分类

下载